Get Even More Visitors To Your Blog, Upgrade To A Business Listing >>

Merz Price or Differential Protection of Power Transformer

Merz Price Protection of Power Transformer

 Merz price circulating current principle is commonly used for the protection of power transformer of 5MVA and and above against earth and phase faults. The system as applied to transformers fundamentally the same as that for generators, but with certain complicated features not encountered in the generator protection system. They are explained below;

CT Ratios

In a power transformer, currents in the primary and secondary are to be compared. These currents will be different, due to primary and secondary voltages being different. Hence the difference is compensated by different turn’s ratios of CTs. If N is the turn’s ratio of power transformer, then the turns ratio of the CTs on the LV side is made N times of the CTs on the HV side. In this condition, the secondaries of the two CTs will carry identical currents under normal conditions. Consequently, there will not be any differential current flowing thro’ the relay and hence it remains inoperative.

CT Connections

There is usually a Phase difference between the primary and secondary current s of a 3-phase power transformer. Even if CTs of proper turns ratio are used, a differential connection for phase difference is effected by appropriate connections for CTs. The CTs on one side if the transformer, are connected in such a way the resultant currents fed into the pilot wires are displaced in phase from the individual phase currents in the same direction as and by an angle equal to the phase shift between the power transformer primary and secondary currents.
  • Read : Leakage Reactance of Core Type Transformer
  • Read : Cooling Methods of Transformer

The power transformers are grouped according the phase displacements as below [as per IS 2026-1962].
Group 1 : Star-star, phase displacement = 0o
Group 2 : star-star, phase displacement = 180o
Group 3 : Delta-star, Phase displacement = –30o
Group 4 : Delta-star, phase displacement = +30o

In order to make the currents in both side CTs (HV and LV side CTs) in phase, the following rules are followed.

Secondaries of CTs on star connected side of power transformer are connected in delta as shown in the figure below:
 
 
Secondary’s of CTs on delta connected side of power transformer are connected is star shown in fig below.
 
 
With such an arrangement, the phase displacement between currents gets cancelled with the phase displacement due to secondary current.
The table below shows the type of connections to be employed for CTs, in order to compensate for the phase difference in the primary and secondary currents in the transformer.
S. No
Power Transformer Connection
Current Transformer Connection
Primary
Secondary
Primary
Secondary
1
Star (with Neutral Earthed)
Delta
Delta
Star
2
Delta
Delta
Star
Star
3
Star
Star (with Neutral Earthed)
Delta
Delta
4
Delta
Star (with Neutral Earthed)
Star
Delta

Merz-price Differential Protection for Delta-Delta Power Transformer

It can be seen that for a delta/star power transformer, the CTs on the delta side should be connected in star and those connected in delta are the ones in the star side.

The figure shows merz price differential protection for delta/delta 3 –phase power transformer. The CTs on the both sides are connected in star. This is to compensate for the phase difference between the power transformer primary and secondary currents. The CTs are connected by pilot wires and one relay is used for each pair of CTs.
 
 
During normal i.e., no-fault conditions, the secondaries of CTs carry identical currents. Therefore the currents entering and leaving the pilot wires at both ends are the same and no current flows through (OC) of the relays. If a ground or phase to phase faults occurs, the currents in the CT secondary’s will no longer be the same and the differential current flowing through the relay circuit will make the breaker on both sides of the power transformer to trip.

This scheme also protection for short circuits between turns on the same phase winding. When a short circuit occurs between the turns, the turn’s ratio of the power transformer is altered and causes unbalance in current transformer pairs. When enough differential current flows through the relay, it acts and clears the fault.


This post first appeared on My Tech Info, please read the originial post: here

Share the post

Merz Price or Differential Protection of Power Transformer

×

Subscribe to My Tech Info

Get updates delivered right to your inbox!

Thank you for your subscription

×